Guidance Potential failure of High-Voltage (HV) 11KV Switchgear – Schneider Electric (Merlin Gerin) Ringmaster RN2c, RE2c and RN6c ring main units Potential failure of the Merlin Gerin Ring
Main Unit to isolate and Earth as shown on the position indicator window.
From: Department of Health and Social Care Published 29 November 2011 Get emails about this page Applies to England Documents Download EFA/2011/004: High-Voltage (HV) 11KV Switchgear –
Schneider Electric (Merlin Gerin) Ringmaster PDF, 124 KB, 3 pages
This file may not be suitable for users of assistive technology.
Request an accessible format. If you use assistive technology (such as a screen reader) and need a version of thisdocument in a more accessible format, please email [email protected]. Please tell us what format you need. It will help us if you say what assistive technology you use. Details
Problem identified
Potential failure of the Merlin Gerin Ring Main Unit to isolate and Earth as shown on the position indicator window.
Cable can still be LIVE even when switching indicator shows the switch gear in each the positions OFF and EARTH ON.